APG 1313-6

APG 1313-6

Fuel Type Natural Gas
3Phalse
60hz
    • 277/480V
    • kVA

    • kW

    • Power Prime

    • 1180

    • 944.00

    • Power Standby

    • 1313

    • 1050.40

General Features

  • Model Name APG 1313-6

  • Frequency (Hz) 60

  • Fuel Type Used Natural Gas

  • Engine Brand and Model PSI - 53L

  • Alternator Brand and Model Mecc Alte - ECO 43-1M/4 A

  • Control Panel Model DSE 7320

  • Cabinet AUL 40ft HC

Product Features

  • altEngine Specifications
  • altAlternator Features
  • altControl Panel Features
  • altCabin Features
  • altDimensions and Weights

Tab 1

  • Producer

  • PSI

  • Engine Model

  • 53L

  • Cylinder and Design

  • 16 cylinders - V type

  • Bore and Stroke (mm)

  • 150 (5,9) X 185 (7,3)

  • Total Cylinder Volume (L)

  • 52,3 (3192)

  • Compression Ratio

  • 10.5 : 1

  • Engine Speed (rpm)

  • 1800

  • Standby Power (kW/hp)

  • 1185 (1589)

  • Prime Power(kW/hp)

  • 1067 (1431)

  • Block Heater (Adt)

  • 1

  • Block Heater Power (Watt)

  • 3000

  • Governor System

  • ECU

  • Air Filter<br>

  • Dry Type

  • Air intake

  • Turbo Charged

  • Oil Capacity (L)

  • 171 (45,2)

  • Max. Oil Temperature ⁰C (F)

  • 121 (250)

  • Fuel Type

  • Natural Gas

  • Injection Type

  • Spark-Ignited

  • Fuel Pump Type

  • -

  • Operating Voltage (Vdc)

  • 24 Vdc

  • Battery and Capacity (Unit/Ah)

  • 2/143

  • Cooling Method

  • Water Cooled

  • Coolant Capacity (engine only)l (gal)

  • 100 (26,4)

  • Exhaust Gas Flow (m³/min)

  • 175

  • Exhaust Gas Temperature ⁰C (F)

  • 649 (1200)

  • Total Cooling Water Capacity (l)

  • 248 (65,4)

  • Cooling Fan Air Flow m³/min (ft³/min)

  • 1906

  • Fuel Consumption at 50% Prime Load l/h (kg/h)

  • 182 (130)

  • Fuel Consumption at 75% Prime Load l/h (kg/h)

  • 251 (180)

  • Fuel Consumption at 100% Prime Load l/h (kg/h)

  • 324 (233)

Tab 2

  • Producer

  • Mecc Alte

  • Alternatrr Model

  • ECO 43-1M/4 A

  • Frequency (Hz)

  • 60

  • Power (kVA)

  • 1250

  • Voltage (V)

  • 480

  • Phalse

  • 3

  • A.V.R.

  • DER1

  • Voltage Regulation

  • 0.5

  • Insulation Class

  • H

  • Protection Class

  • IP23

  • Nominal Power Factor

  • 0.8

  • Total Generator Weight (kg)

  • 2275

  • Cooling Air (m³/min)

  • 108

Tab 3

  • Generator and Control Module Model

  • DSE 7320

  • 1. Menu navigation buttons 
    2. Close mains button 
    3. Main Status and instrumentation display 
    4. Alarm LED's 
    5. Close generator button 
    6. Status LED's 
    7. Operation selecting buttons
  • Standard Devices

  • DSE model 7320, Auto Mains Failure control module, with a highly sophisticated level of new features and functions

    Static battery charger, Fuses for control circuits

  • Control Unit

  • - The DSE 7320 control module is a standard addition to our generator sets from 220 kVA upwards and it has been

    designed to start and stop diesel and gas generating sets that include electronic and non electronic engines.

    - The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is therefore suitable

    for controlling a standby generating set in conjunction with an automatic transfer switch.

    - The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and

    indicating faults by means of its LCD display on the front panel.

  • Construction and Painting

  • - Components installed in sheet steel enclosure.

    - Phosphate chemical, pre-coating of steel provides corrosion resistant surface

    - Polyester composite powder topcoat forms high gloss and extremely durable finish

    - Lockable hinged panel door provides for easy component access

  • Assembly

  • The Control panel is mounted at the generating set baseframe on robust steel stand or power module. Located at side

    of generating set with properly panel visibility.

  • -Engine speed

    -Oil pressure

    -Coolant temperature

    -Run time

    -Battery volts

    -Engine maintenance due

  • -Fail to start

    -Emergency stop

    -Low oil pressure

    -High engine temperature

    -Low coolant level

    -Under/over speed

    -Under/over generator frequency

    -Under/over generator voltage

    -Oil pressure sensor open

    -Phase rotation

  • -Charge failure

    -Battery under voltage

    -Fail to stop

    -Low fuel level (opt.)

    -kW over load

    -Negative phase sequence

    -Loss of speed signal

  • -Voltage (L-L, L-N)

    -Current (L1-L2-L3)

    -Frequency

    -Earthcurrent

    -kW

    -Pf

    -kVAr

    -kWh, kVAh, kVArh

    -Phasesequence

  • -Earth fault

    -kW over load

    -Generator over current

    -Negative phase sequence

  • -Voltage (L-L, L-N)

    -Frequency

  • Options

  • - High oil temperature shut down

    - Low fuel level shut down

    - Low fuel level alarm

    - High fuel level alarm

  • Options Control Panel Compatibility List

  • - Electrical Safety / Electro Magnetic Compatibility (EMC)

    - BS EN 61000-6-2 EMC Generic Immunity Standard

    - BS EN 61000-6-4 EMC Generic Emission Standard

    - BS EN 60950 Electrical Safety

  • Static Battery Charger

  • - Battery charger is manufactured with switching-mode and SMD technology and it has high efficiency.

    - Battery charger models' output V-I characteristic is very close to square

    - 2405 has fully output shot circuit protection and it can be used as a current source.

    - 2405 charger has high efficiency, long life, low failure rate, light-weight and low heat radiated in accordance

    with linear alternatives.

    - The charger is fitted with a protection diode across the output.

    - Charge fail output is available.

    - Connect charge fail relay coil between positive output and CF output.

    - Input: 196-264V.

    - Output: 27,6V 5A or 13,8V 5A.

Tab 4

  • Canopy

  • AUL 40ft HC

  • Length (mm)

  • 12192 (480)

  • Width (mm)

  • 2438 (96)

  • Height (mm)

  • 2896 (114)

Tab 5

Tab 1

alt

*Images are for illustrative purposes only; actual presentation may vary.

    • Open Group
    • Length (mm)(A)
    • Width (mm)(B)
    • Height (mm)(C)
    • Gross Weight Dry (kg.)
    • Full Tank Capacity (lt.)
    • -
    • -
    • -
    • -
    • -

Tab 2

alt

*Görseller temsilidir, sunumları farklılık gösterebilir.

    • Canopy Group
    • Length (mm)(A)
    • Width (mm)(B)
    • Height (mm)(C)
    • Gross Weight Dry (kg.)
    • Full Tank Capacity (lt.)
    • AUL 40ft HC
    • 12192 (480)
    • 2438 (96)
    • 2896 (114)
    • -
    • fueL_TANK_DETAILS_DRWGS

Optional Equipment

Certificates

Directive

- 2006/42/EC : Machinery Safety Directive

- 2004/108/EC : Electromagnetic Compatibility Directive

- 2006/95/EC : Low Voltage Directive

Standarts

- EN ISO 8528-13:2016 : Reciprocating internal combustion engine-driven alternating current generating sets- Part:13: Safety

(Türkçe)

(English)

(French)

(Spanish)

(Russian)