AC 550 - GTS

AC 550 - GTS

Fuel Type Diesel
3Phalse
50hz
    • 230/400V
    • kVA

    • kW

    • Power Prime

    • 500

    • 400.0

    • Power Standby

    • 550

    • 440.0

General Features

  • Model Name AC 550 - GTS

  • Frequency (Hz) 50

  • Fuel Type Used Diesel

  • Engine Brand and Model Cummins - KTA19-G4

  • Alternator Brand and Model Stamford - HCI544C

  • Control Panel Model InteliMains NT

  • Cabinet GTS 20

Product Features

  • altEngine Specifications
  • altAlternator Features
  • altControl Panel Features
  • altCabin Features
  • altDimensions and Weights

Tab 1

  • Producer

  • Cummins

  • Engine Model

  • KTA19-G4

  • Cylinder and Design

  • 6 cylinders - in line

  • Bore and Stroke (mm)

  • 159 X 159

  • Total Cylinder Volume (L)

  • 18.9

  • Compression Ratio

  • 13.9:1

  • Engine Speed (rpm)

  • 1500

  • Standby Power (kW/hp)

  • 504/675

  • Prime Power(kW/hp)

  • 448/600

  • Block Heater (Adt)

  • 1

  • Block Heater Power (Watt)

  • 3000

  • Governor System

  • Electronic

  • Air Filter<br>

  • Dry Type

  • Air intake

  • Turbo Charged and After Cooled

  • Oil Capacity (L)

  • 50

  • Max. Oil Temperature ⁰C (F)

  • 121

  • Fuel Type

  • Diesel

  • Injection Type

  • Direct

  • Fuel Pump Type

  • Cummins PT

  • Operating Voltage (Vdc)

  • 24 Vdc

  • Battery and Capacity (Unit/Ah)

  • 2x120

  • Cooling Method

  • Water Cooled

  • Coolant Capacity (engine only)l (gal)

  • 30

  • Exhaust Gas Flow (m³/min)

  • 96.24

  • Exhaust Gas Temperature ⁰C (F)

  • 557

  • Total Cooling Water Capacity (l)

  • 120

  • Fuel Consumption at 50% Prime Load l/h (kg/h)

  • 57

  • Fuel Consumption at 75% Prime Load l/h (kg/h)

  • 82

  • Fuel Consumption at 100% Prime Load l/h (kg/h)

  • 107

Tab 2

  • Producer

  • Stamford

  • Alternatrr Model

  • HCI544C

  • Frequency (Hz)

  • 50

  • Power (kVA)

  • 500

  • Voltage (V)

  • 400

  • Phalse

  • 3

  • A.V.R.

  • AS440

  • Voltage Regulation

  • 1

  • Insulation Class

  • H

  • Protection Class

  • IP23

  • Nominal Power Factor

  • 0.8

  • Total Generator Weight (kg)

  • 1263

  • Cooling Air (m³/min)

  • 62.1

Tab 3

  • Generator and Control Module Model

  • InteliMains NT

  • 1. Start
    2. Stop
    3. Mode > OFF > MAN > AUT > TEST
    4. Fault Reset
    5. Mode < OFF < MAN < AUT < TEST
    6. Horn Reset
    7. GCB control (Open/Close)
    8. MCB control (Open/Close)
    9. Enter
    10. 5% Increase of edited setpoint`s value.
    11. 5% decrease of edited setpoint`s value.
    12. Decrease setpoint value.
    13. Increase setpoint value.
    14. Escape.
  • Standard Devices

  • • 6 Binary Outputs
    • 6 Binary Inputs
    • Mains and Bus Voltage measurement (3-phase)
    • Mains Current measurement (3-phase)
    • Auxiliary Current measurement (1-phase)
    • RS485 Communication port for universal use
    • RS232 Communication port
    • CAN1 Communication port (for extension modules)
    • CAN2 Communication port (for intercontroller communication and monitoring) 
     
  • Control Unit

  • InteliMains-NT controller is comprehensive mains supervision controller for multiple generating sets operating in parallel to the Mains. A modular construction allow upgrades to different levels of complexity in order to provide the best solution for various customer applications.
    NT Family controllers are equipped with a powerful graphic display showing icons, symbols and bargraphs for intuitive operation, which sets, together with high functionality, new standards in Gen-setcontrols.
    The controller automatically connects and synchronizes two parts of bus bar and controls the bus tie circuit breaker (BTB).
  • Construction and Painting

  • Components installed in a sheet steel enclosure.
    Phosphate chemical, pre-coating of steel provides corrosion resistant surface.
    Polyester composite powder topcoat forms high gloss and an extremely durable finish.
    Lockable hinged panel door provides for easy component access.
  • Assembly

  • Prepare the screw holders
    Locate four sockets for screw holders
    Insert the unit into cut-out in a switchboard and insert all four screw holders accordingly to their positions
    Tighten as required to fix the controller in the position
  • • BTB controlled by InteliMains-NT
    • Highly customizable behavior of breaker control (dead bus, blockation of closing etc.)
    • Synchronization (voltage and phase matching) of two control groups separated by InteliMainsBTB with various settings (which group synchronizes to which etc.)
    • Load shedding control (based on power transferred via BTB)
    • Full PLC logic included (useful in complex systems – BTB can for example serve as auxiliary PLC for other controllers)
    • Support of redundancy controller
    • Full set of protections for BusL and additional protections for BusR
    • Group Link function
    • Active calls and SMS
     
  • Options

  • 8 Binary inputs and 8 Binary outputs packed in a smallunit (HWswitchable to IO16/0)
    16 Binary inputs packed in a smallunit (HWswitchable to IO8/8)
    8 Analog inputs and 1 pulse/frequency input in a smallunit
    8 Thermocouple Analog inputs in a smallunit
    8 Analog inputs packed in a rugged metalunit
    8 Binary inputs, 8 Binary outputs, 4 Analog inputs and 1 Analog output in a unit
    15 Binary LEDoutput (3 colors)packed in a rugged metalunit
    8 Analog outputs packed in a rugged metalunit
    Multiple Internet connections (PCand Modbus)to allcontrollers on CAN2 orRS485
    Direct connection (PC)to allcontrollers on CAN2 orRS485
  • Options Control Panel Compatibility List

  • • EN 60068-2-6 ed.2:2008
    • EN 60068-2-27 ed.2:2010
    • EN 60068-2-30, May2000
    • EN 60068-2-64 EN 61010-1:2003
     
  • Static Battery Charger

  • Battery charger is manufactured with switching-mode and SMD technology and it has high efficiency.
    Battery charger models' output V-I characteristic is very close to square
    2405 has fully output short circuit protection and ıt can be used as a current source.
    2405 charger has high efficiency, long life, low failure rate, lightweight and low heat radiated in accordance with linear alternatives.
    The charger is fitted with a protection diode across the output.
    Charge fail output is available.
    Connect charge fail relay coil between the positive output and CF output.
    Input: 196-264V.
    Output: 27,6V 5A or 13,8V 5A.

Tab 4

  • Canopy

  • GTS 20

  • 1. Steel structures. 
    2. Emergency stop push button. 
    3. Control panel is mounted on the baseframe . Located at the right side of the generator set. 
    4. Corrosion-resistant locks and hinges. 
    5. Oil could be drained via valve and a hose 
    6. Exhaust system in the canopy. 
    7. Special large access doors for easy maintenance 
    8. In front and back side special large access doors for easy maintenance 
    9. Base frame -fuel tank. 
    10. Lifting points similar to ISO container, located on each top corner of the canopy. 
    11. The cap on the canopy provides easy access to radiator cap. 
    12. Soundproofing materials 
    13. Plastic air intake pockets.

  • Introductıon

  • Sound-attenuated and weather-protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.

  • General Characteristics

  • Compact footprint, low profile design. 
    Enclosure, generator set, exhaust system and fuel tank are pre-assembled, pre-integrated and shipped as one package 
    Body made from steel components treated with polyester powder coating 
    Fire retardant foam insulation 
    Easy access to all service points 
    Exhaust system inside canopy 
    Large doors on each side 
    Control panel viewing window in a lockable access door 
    Emergency stop push button mounted on enclosure exterior 
    Cooling fan and battery charging alternator fully guarded 
    Fuel fill and battery can only be reached via lockable access doors. 
    Lifting points on the top of canopy and base frame 
    Customer options available to meet your application's needs. 
    Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been approved by the notified body Szutest

  • Length (mm)

  • 5000

  • Width (mm)

  • 2200

  • Height (mm)

  • 2468

  • Fuel Tank Capacity (l)

  • 850

Tab 5

Tab 1

alt

*Images are for illustrative purposes only; actual presentation may vary.

    • Open Group
    • Length (mm)(A)
    • Width (mm)(B)
    • Height (mm)(C)
    • Gross Weight Dry (kg.)
    • Full Tank Capacity (lt.)
    • 3205
    • 1550
    • 2091
    • 3850
    • 850

Tab 2

alt

*Görseller temsilidir, sunumları farklılık gösterebilir.

    • Canopy Group
    • Length (mm)(A)
    • Width (mm)(B)
    • Height (mm)(C)
    • Gross Weight Dry (kg.)
    • Full Tank Capacity (lt.)
    • GTS 20
    • 5000
    • 2200
    • 2468
    • 4860
    • fueL_TANK_DETAILS_DRWGS

Optional Equipment

  • altEngine
  • altAlternator
  • altCabin
  • altControl Panel
  • altTransfer Board
  • altAuxiliary Equipment
  • altExhaust
  • altCabin Optionall

Engine

- Fuel-Water Seperator Filter

- Oil heater

Alternator Characteristics

- Anti-Condensation Heater

- Over sized alternator

- PMG excitation + AVR

- Main line circuit breaker

Canopy Characteristics

- Galvanized Coating

- ISO Container

- Marine Grade Paint

Control Panel

- Automatic synchronising and power control system (Multi gen-set Parallel)

- Parallel system with mains

- Transition synchronization with mains

- Alarm output relays

- Earth fault, single set

- Parallel system with mains

- Remote relay output

- Remote communication with modem

- Charge Ammeter

Transfer Panel

- Three or four pole contactor

- Three or four pole motor operated circuit breaker

Auxiliary Equipment

- Main Fuel Tank

- Automatic or manual fuel filling system

- Electrical or manual oil drain pump

- Low and high fuel level alarm

- Inlet and outlet motorized louvers

- Inlet and outlet acoustic baffles

- Tool kit for maintenance

- 1500/3000 hours maintenance kit

- Supplied with oil and coolant (-30°C)

Exhaust

- Residential Silencer

- Silencer Spark Arrester

- Critical Silencer

- Catalytic Convertor

Canopy Optional Alternator and Control Panel

Please contact to your reseller for additional Alternator, Control Panel and Breaker Switch options.

Certificates

Directive

- 2006/42/EC : Machinery Safety Directive

- 2014/30/EU : Electromagnetic Compatibility Directive

- 2014/35/EU : Low Voltage Directive

Standarts

- TS ISO 8528-5:2022 / TS EN ISO 8528-13:2018 : Reciprocating internal combustion engine-driven alternating

current generating sets- Part:13: Safety


Quality Management Systems

ISO 9001:2015

ISO 14001:2015

ISO 45001:2018

ISO 50001:2018

ISO 27001:2013

ISO 10002:2018


(Türkçe)

(English)