1. Start 2. Stop 3. Mode > OFF > MAN > AUT > TEST 4. Fault Reset 5. Mode < OFF < MAN < AUT < TEST 6. Horn Reset 7. GCB control (Open/Close) 8. MCB control (Open/Close) 9. Enter 10. 5% Increase of edited setpoint`s value. 11. 5% decrease of edited setpoint`s value. 12. Decrease setpoint value. 13. Increase setpoint value. 14. Escape.
Standard Devices
• 6 Binary Outputs
• 6 Binary Inputs
• Mains and Bus Voltage measurement (3-phase)
• Mains Current measurement (3-phase)
• Auxiliary Current measurement (1-phase)
• RS485 Communication port for universal use
• RS232 Communication port
• CAN1 Communication port (for extension modules)
• CAN2 Communication port (for intercontroller communication and monitoring)
Control Unit
InteliMains-NT controller is comprehensive mains supervision controller for multiple generating sets operating in parallel to the Mains. A modular construction allow upgrades to different levels of complexity in order to provide the best solution for various customer applications.
NT Family controllers are equipped with a powerful graphic display showing icons, symbols and bargraphs for intuitive operation, which sets, together with high functionality, new standards in Gen-setcontrols.
The controller automatically connects and synchronizes two parts of bus bar and controls the bus tie circuit breaker (BTB).
Construction and Painting
Components installed in a sheet steel enclosure.
Phosphate chemical, pre-coating of steel provides corrosion resistant surface.
Polyester composite powder topcoat forms high gloss and an extremely durable finish.
Lockable hinged panel door provides for easy component access.
Assembly
Prepare the screw holders
Locate four sockets for screw holders
Insert the unit into cut-out in a switchboard and insert all four screw holders accordingly to their positions
Tighten as required to fix the controller in the position
• BTB controlled by InteliMains-NT
• Highly customizable behavior of breaker control (dead bus, blockation of closing etc.)
• Synchronization (voltage and phase matching) of two control groups separated by InteliMainsBTB with various settings (which group synchronizes to which etc.)
• Load shedding control (based on power transferred via BTB)
• Full PLC logic included (useful in complex systems – BTB can for example serve as auxiliary PLC for other controllers)
• Support of redundancy controller
• Full set of protections for BusL and additional protections for BusR
• Group Link function
• Active calls and SMS
Options
8 Binary inputs and 8 Binary outputs packed in a smallunit (HWswitchable to IO16/0)
16 Binary inputs packed in a smallunit (HWswitchable to IO8/8)
8 Analog inputs and 1 pulse/frequency input in a smallunit
8 Thermocouple Analog inputs in a smallunit
8 Analog inputs packed in a rugged metalunit
8 Binary inputs, 8 Binary outputs, 4 Analog inputs and 1 Analog output in a unit
15 Binary LEDoutput (3 colors)packed in a rugged metalunit
8 Analog outputs packed in a rugged metalunit
Multiple Internet connections (PCand Modbus)to allcontrollers on CAN2 orRS485
Direct connection (PC)to allcontrollers on CAN2 orRS485
Options Control Panel Compatibility List
• EN 60068-2-6 ed.2:2008
• EN 60068-2-27 ed.2:2010
• EN 60068-2-30, May2000
• EN 60068-2-64 EN 61010-1:2003
Static Battery Charger
Battery charger is manufactured with switching-mode and SMD technology and it has high efficiency.
Battery charger models' output V-I characteristic is very close to square
2405 has fully output short circuit protection and ıt can be used as a current source.
2405 charger has high efficiency, long life, low failure rate, lightweight and low heat radiated in accordance with linear alternatives.
The charger is fitted with a protection diode across the output.
Charge fail output is available.
Connect charge fail relay coil between the positive output and CF output.
Input: 196-264V.
Output: 27,6V 5A or 13,8V 5A.
Tab 4
Canopy
GTS 20
1. Steel structures. 2. Emergency stop push button. 3. Control panel is mounted on the baseframe . Located at the right side of the generator set. 4. Corrosion-resistant locks and hinges. 5. Oil could be drained via valve and a hose 6. Exhaust system in the canopy. 7. Special large access doors for easy maintenance 8. In front and back side special large access doors for easy maintenance 9. Base frame -fuel tank. 10. Lifting points similar to ISO container, located on each top corner of the canopy. 11. The cap on the canopy provides easy access to radiator cap. 12. Soundproofing materials 13. Plastic air intake pockets.
Introductıon
Sound-attenuated and weather-protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
General Characteristics
Compact footprint, low profile design.
Enclosure, generator set, exhaust system and fuel tank are pre-assembled, pre-integrated and shipped as one package
Body made from steel components treated with polyester powder coating
Fire retardant foam insulation
Easy access to all service points
Exhaust system inside canopy
Large doors on each side
Control panel viewing window in a lockable access door
Emergency stop push button mounted on enclosure exterior
Cooling fan and battery charging alternator fully guarded
Fuel fill and battery can only be reached via lockable access doors.
Lifting points on the top of canopy and base frame
Customer options available to meet your application's needs.
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been approved by the notified body Szutest
Length (mm)
5000
Width (mm)
2200
Height (mm)
2468
Fuel Tank Capacity (l)
850
Tab 5
Open Group
Cabin Group
Tab 1