AP 1650

AP 1650

Fuel Type Diesel
3Phalse
50hz
    • 230/400V
    • kVA

    • kW

    • Power Prime

    • 1500

    • 1200.0

    • Power Standby

    • 1650

    • 1320.0

General Features

  • Model Name AP 1650

  • Frequency (Hz) 50

  • Fuel Type Used Diesel

  • Engine Brand and Model Perkins - 4012-46TAG2A

  • Alternator Brand and Model Mecc Alte - ECO 46-1S/4 A

  • Control Panel Model DSE 7320

  • Cabinet AK 98

Product Features

  • altEngine Specifications
  • altAlternator Features
  • altControl Panel Features
  • altCabin Features
  • altDimensions and Weights

Tab 1

  • Producer

  • Perkins

  • Engine Model

  • 4012-46TAG2A

  • Cylinder and Design

  • 12 cylinders - V type

  • Bore and Stroke (mm)

  • 160 X 190

  • Total Cylinder Volume (L)

  • 45.842

  • Compression Ratio

  • 13.0:1

  • Engine Speed (rpm)

  • 1500

  • Standby Power (kW/hp)

  • 1459/1957

  • Prime Power(kW/hp)

  • 1331/1785

  • Block Heater (Adt)

  • 2

  • Block Heater Power (Watt)

  • 3000

  • Governor System

  • Electronic

  • Air Filter<br>

  • Dry Type

  • Air intake

  • Turbo Charged

  • Oil Capacity (L)

  • 177

  • Max. Oil Temperature ⁰C (F)

  • 105

  • Fuel Type

  • Diesel

  • Injection Type

  • Direct

  • Fuel Pump Type

  • Mechanical

  • Operating Voltage (Vdc)

  • 24 Vdc

  • Battery and Capacity (Unit/Ah)

  • 4x143

  • Cooling Method

  • Water Cooled

  • Exhaust Gas Flow (m³/min)

  • 320

  • Exhaust Back Pressure in-Hg (kPa)

  • 5

  • Exhaust Gas Temperature ⁰C (F)

  • 455

  • Total Cooling Water Capacity (l)

  • 195.7

  • Cooling Fan Air Flow m³/min (ft³/min)

  • 1762

  • Fuel Consumption at 50% Prime Load l/h (kg/h)

  • 164

  • Fuel Consumption at 75% Prime Load l/h (kg/h)

  • 236

  • Fuel Consumption at 100% Prime Load l/h (kg/h)

  • 309

Tab 2

  • Producer

  • Mecc Alte

  • Alternatrr Model

  • ECO 46-1S/4 A

  • Frequency (Hz)

  • 50

  • Power (kVA)

  • 1500

  • Voltage (V)

  • 400

  • Phalse

  • 3

  • A.V.R.

  • DER1

  • Voltage Regulation

  • 0.5

  • Insulation Class

  • H

  • Protection Class

  • IP23

  • Nominal Power Factor

  • 0.8

  • Total Generator Weight (kg)

  • 3010

  • Cooling Air (m³/min)

  • 135

Tab 3

  • Generator and Control Module Model

  • DSE 7320

  • 1. Menu navigation buttons 
    2. Close mains button 
    3. Main Status and instrumentation display 
    4. Alarm LED's 
    5. Close generator button 
    6. Status LED's 
    7. Operation selecting buttons
  • Standard Devices

  • DSE model 7320, Auto Mains Failure control module, with a highly sophisticated level of new features and functions

    Static battery charger, Fuses for control circuits

  • Control Unit

  • - The DSE 7320 control module is a standard addition to our generator sets from 220 kVA upwards and it has been

    designed to start and stop diesel and gas generating sets that include electronic and non electronic engines.

    - The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is therefore suitable

    for controlling a standby generating set in conjunction with an automatic transfer switch.

    - The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and

    indicating faults by means of its LCD display on the front panel.

  • Construction and Painting

  • - Components installed in sheet steel enclosure.

    - Phosphate chemical, pre-coating of steel provides corrosion resistant surface

    - Polyester composite powder topcoat forms high gloss and extremely durable finish

    - Lockable hinged panel door provides for easy component access

  • Assembly

  • The Control panel is mounted at the generating set baseframe on robust steel stand or power module. Located at side

    of generating set with properly panel visibility.

  • -Engine speed

    -Oil pressure

    -Coolant temperature

    -Run time

    -Battery volts

    -Engine maintenance due

  • -Fail to start

    -Emergency stop

    -Low oil pressure

    -High engine temperature

    -Low coolant level

    -Under/over speed

    -Under/over generator frequency

    -Under/over generator voltage

    -Oil pressure sensor open

    -Phase rotation

  • -Charge failure

    -Battery under voltage

    -Fail to stop

    -Low fuel level (opt.)

    -kW over load

    -Negative phase sequence

    -Loss of speed signal

  • -Voltage (L-L, L-N)

    -Current (L1-L2-L3)

    -Frequency

    -Earthcurrent

    -kW

    -Pf

    -kVAr

    -kWh, kVAh, kVArh

    -Phasesequence

  • -Earth fault

    -kW over load

    -Generator over current

    -Negative phase sequence

  • -Voltage (L-L, L-N)

    -Frequency

  • Options

  • - High oil temperature shut down

    - Low fuel level shut down

    - Low fuel level alarm

    - High fuel level alarm

  • Options Control Panel Compatibility List

  • - Electrical Safety / Electro Magnetic Compatibility (EMC)

    - BS EN 61000-6-2 EMC Generic Immunity Standard

    - BS EN 61000-6-4 EMC Generic Emission Standard

    - BS EN 60950 Electrical Safety

  • Static Battery Charger

  • - Battery charger is manufactured with switching-mode and SMD technology and it has high efficiency.

    - Battery charger models' output V-I characteristic is very close to square

    - 2405 has fully output shot circuit protection and it can be used as a current source.

    - 2405 charger has high efficiency, long life, low failure rate, light-weight and low heat radiated in accordance

    with linear alternatives.

    - The charger is fitted with a protection diode across the output.

    - Charge fail output is available.

    - Connect charge fail relay coil between positive output and CF output.

    - Input: 196-264V.

    - Output: 27,6V 5A or 13,8V 5A.

Tab 4

  • Canopy

  • AK 98

  • 1. Steel structure made from steel sheet and steel profiles. 
    2. Canopy and panels made from powder-coated sheet steel. 
    3. Emergency stop push button. 
    4. Control panel is mounted on the baseframe . Located at the back of the generator set 
    5. Cables out locations are under of the canopy. 
    6. Corrosion-resistant locks and hinges. 
    7. Oil could be drained via valve and a hose 
    8. Exhaust system on the canopy. 
    9. special large access doors (marine type) for easy maintenance 
    10. Fuel tank is at front of the canopy,easy access to the fuel tank via lockable door. 
    11. Lifting points similar to ISO container, located on each top corner of the canopy. 
    12. The cap on the canopy provides easy access to the radiator cap. 
    13. Soundproofing materials 
    14. Integrated ladder built on the side of the canopy allows access to the top of the canopy.

  • Introductıon

  • Sound-attenuated and weather-protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.

  • General Characteristics

  • Compact footprint, low profile design. 
    Enclosure, generator set, exhaust system and fuel tank are pre-assembled, pre-integrated and shipped as one package 
    Body made from steel components treated with polyester powder coating 
    Fire retardant foam insulation 
    Easy access to all service points 
    Exhaust system inside canopy 
    Large doors on each side 
    Control panel viewing window in a lockable access door 
    Emergency stop push button mounted on enclosure exterior 
    Cooling fan and battery charging alternator fully guarded 
    Fuel fill and battery can only be reached via lockable access doors. 
    Lifting points on the top of canopy and base frame 
    Customer options available to meet your application's needs. 
    Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been approved by the notified body Szutest

  • Length (mm)

  • 9000

  • Width (mm)

  • 2270

  • Height (mm)

  • 2581

  • Fuel Tank Capacity (l)

  • 1900

Tab 5

Tab 1

alt

*Images are for illustrative purposes only; actual presentation may vary.

    • Open Group
    • Length (mm)(A)
    • Width (mm)(B)
    • Height (mm)(C)
    • Gross Weight Dry (kg.)
    • Full Tank Capacity (lt.)
    • 4920
    • 2151
    • 2438
    • 10200
    • 2000

Tab 2

alt

*Görseller temsilidir, sunumları farklılık gösterebilir.

    • Canopy Group
    • Length (mm)(A)
    • Width (mm)(B)
    • Height (mm)(C)
    • Gross Weight Dry (kg.)
    • Full Tank Capacity (lt.)
    • AK 98
    • 9000
    • 2270
    • 2581
    • 14300
    • fueL_TANK_DETAILS_DRWGS

Optional Equipment

  • altEngine
  • altAlternator
  • altCabin
  • altControl Panel
  • altTransfer Board
  • altAuxiliary Equipment
  • altExhaust
  • altCabin Optionall

Engine

- Fuel-Water Seperator Filter

- Oil heater

Alternator Characteristics

- Anti-Condensation Heater

- Over sized alternator

- PMG excitation + AVR

- Main line circuit breaker

Canopy Characteristics

- Galvanized Coating

- ISO Container

- Marine Grade Paint

Control Panel

- Automatic synchronising and power control system (Multi gen-set Parallel)

- Parallel system with mains

- Transition synchronization with mains

- Alarm output relays

- Earth fault, single set

- Parallel system with mains

- Remote relay output

- Remote communication with modem

- Charge Ammeter

Transfer Panel

- Three or four pole contactor

- Three or four pole motor operated circuit breaker

Auxiliary Equipment

- Main Fuel Tank

- Automatic or manual fuel filling system

- Electrical or manual oil drain pump

- Low and high fuel level alarm

- Inlet and outlet motorized louvers

- Inlet and outlet acoustic baffles

- Tool kit for maintenance

- 1500/3000 hours maintenance kit

- Supplied with oil and coolant (-30°C)

Exhaust

- Residential Silencer

- Silencer Spark Arrester

- Critical Silencer

- Catalytic Convertor

Canopy Optional Alternator and Control Panel

Please contact to your reseller for additional Alternator, Control Panel and Breaker Switch options.

Certificates

Directive

- 2006/42/EC : Machinery Safety Directive

- 2014/30/EU : Electromagnetic Compatibility Directive

- 2014/35/EU : Low Voltage Directive

Standarts

- TS ISO 8528-5:2022 / TS EN ISO 8528-13:2018 : Reciprocating internal combustion engine-driven alternating

current generating sets- Part:13: Safety


Quality Management Systems

ISO 9001:2015

ISO 14001:2015

ISO 45001:2018

ISO 50001:2018

ISO 27001:2013

ISO 10002:2018


(Türkçe)

(English)

(French)

(Spanish)

(Russian)