AJD 132

AJD 132

Fuel Type Diesel
3Phalse
50hz
    • 230/400V
    • kVA

    • kW

    • Power Prime

    • 120

    • 96.0

    • Power Standby

    • 132

    • 105.6

General Features

  • Model Name AJD 132

  • Frequency (Hz) 50

  • Fuel Type Used Diesel

  • Engine Brand and Model John Deere - 4045HFG20 (122kW)

  • Alternator Brand and Model Mecc Alte - ECP 34-1M/4 C

  • Control Panel Model DSE 6120

  • Cabinet AK 49

Product Features

  • altEngine Specifications
  • altAlternator Features
  • altControl Panel Features
  • altCabin Features
  • altDimensions and Weights

Tab 1

  • Producer

  • John Deere

  • Engine Model

  • 4045HFG20 (122kW)

  • Cylinder and Design

  • 4 cylinders - in line

  • Bore and Stroke (mm)

  • 106 X 127

  • Total Cylinder Volume (L)

  • 4.5

  • Compression Ratio

  • 17.0:1

  • Engine Speed (rpm)

  • 1500

  • Standby Power (kW/hp)

  • 122/164

  • Prime Power(kW/hp)

  • 112/150

  • Block Heater (Adt)

  • 1

  • Block Heater Power (Watt)

  • 750

  • Governor System

  • Mechanic

  • Air Filter<br>

  • Dry Type

  • Air intake

  • Turbocharged and Air Aftercooled

  • Oil Capacity (L)

  • 20.5

  • Fuel Type

  • Diesel

  • Injection Type

  • Direct Injection

  • Fuel Pump Type

  • Delphi DP100G

  • Operating Voltage (Vdc)

  • 12 Vdc

  • Battery and Capacity (Unit/Ah)

  • 1x66

  • Cooling Method

  • Water Cooled

  • Coolant Capacity (engine only)l (gal)

  • 9

  • Exhaust Gas Flow (m³/min)

  • 23.6

  • Exhaust Back Pressure in-Hg (kPa)

  • 7.5

  • Exhaust Gas Temperature ⁰C (F)

  • 610

  • Total Cooling Water Capacity (l)

  • 23

  • Fuel Consumption at 50% Prime Load l/h (kg/h)

  • 15.1

  • Fuel Consumption at 75% Prime Load l/h (kg/h)

  • 21.6

  • Fuel Consumption at 100% Prime Load l/h (kg/h)

  • 28.3

Tab 2

  • Producer

  • Mecc Alte

  • Alternatrr Model

  • ECP 34-1M/4 C

  • Frequency (Hz)

  • 50

  • Power (kVA)

  • 125

  • Voltage (V)

  • 400

  • Phalse

  • 3

  • A.V.R.

  • DSR

  • Voltage Regulation

  • 1

  • Insulation Class

  • H

  • Protection Class

  • IP23

  • Nominal Power Factor

  • 0.8

  • Total Generator Weight (kg)

  • 370

  • Cooling Air (m³/min)

  • 29.2

Tab 3

  • Generator and Control Module Model

  • DSE 6120

  • 1. Menu navigation buttons 
    2. Close mains button 
    3. Main Status and instrumentation display 
    4. Alarm LED's 
    5. Close generator button 
    6. Status LED's 
    7. Operation selecting buttons
  • Standard Devices

  • DSE model 6120, Auto Mains Failure control module, Static battery charger input 198-264 volt, output 27,6V 5A (24V) or

    13,8 Volt 5A (12V), fuses for control circuits. This Control Module is suitable for a wide variety of single gen-set applications

  • Control Unit

  • - The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant

    temperature running hours and battery volts.

    - Module monitors the mains supply and control the switch over to the generator when the mains power fails.

    - The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving

    true first up fault condition of Gen. Set failure.The LCD display indicates the fault.

  • Construction and Painting

  • Components installed in sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion corrosion-resistant surface. Polyester composite powder topcoat forms a high gloss and extremely durable finish. Lockable and hinged panel door provides easy access to components.

  • Assembly

  • Control panel is mounted on baseframe with steel stand. Located at the right side of the generator set (When you look at the Gen.Set. from Alternator side)

  • - Engine speed

    - Oil pressure

    - Coolant temperature

    - Run time

    - battery volts

    - Configurable timing

  • - Fail to start

    - Emergency stop

    - Low oil pressure

    - High coolant temperature

    - Over /Under speed

    - Under/over generator frequency

    - Under/over generator voltage

    - Oil pressure sensor open

    - Coolant temperature sensor open

  • - Charge failure

    - Battery Low/High voltage

    - Fail to stop.

    - Low /High generator voltage

    - Under /Over generator frequency

    - Over /Under speed

    - Low oil pressure

    - High coolant temperature

  • - Voltage (L-L, L-N)

    - Current (L1-L2-L3)

    - Frequency

    - Gen. Set ready

    - Gen. Set enabled

  • - Generator over current

  • - Mains ready

    - Mains enabled

  • Options

  • - Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)

    - Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).

  • Options Control Panel Compatibility List

  • - Electrical Safety / Electro Magenetic Compatibility (EMC)

    - BS EN 60950 Electrical Safety

    - BS EN 61000-6-2 EMC Generic Immunity Standard

    - BS EN 61000-6-4 EMC Generic Emission Standard

  • Static Battery Charger

  • - Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.

    - Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and

    27,6 V for 24 V . Input 198 - 264 volt AC.

    - The charger is fitted with a protection diode across the output.

    - Connect charge fail relay coil between positive output and CF output.

    - They are equipped with RFI filter to reduce electrical noise radiated from the device.

    - Galvanically isolated input and output typically 4kV for high reliability.

Tab 4

  • Canopy

  • AK 49

  • 1. Steel structures 
    2. Emergency stop push button 
    3. Control panel is right side of the set. 
    4. Corrosion.resistant locks and hinges 
    5. Sump drains valves 
    6. Sound proof foam metarial 
    7. Lifting Points 

  • Introductıon

  • Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.

  • General Characteristics

  • Compact footprint, low profile design. 
    Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package 
    Body made from steel components treated with polyester powder coating 
    Fire retardant foam insulation 
    Easy access to all service points 
    Exhaust system inside canopy 
    Large doors on each side 
    Control panel viewing window in a lockable access door 
    Emergency stop push button mounted on enclosure exterior 
    Cooling fan and battery charging alternator fully guarded 
    Fuel fill and battery can only be reached via lockable access doors. 
    Lifting points on the top of canopy and base frame 
    Customer options available to meet your applications needs. 
    Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest

  • Length (mm)

  • 3404

  • Width (mm)

  • 1136

  • Height (mm)

  • 2020

  • Fuel Tank Capacity (l)

  • 340

Tab 5

Tab 1

alt

*Images are for illustrative purposes only; actual presentation may vary.

    • Open Group
    • Length (mm)(A)
    • Width (mm)(B)
    • Height (mm)(C)
    • Gross Weight Dry (kg.)
    • Full Tank Capacity (lt.)
    • 2300
    • 1080
    • 1618
    • -
    • 340

Tab 2

alt

*Görseller temsilidir, sunumları farklılık gösterebilir.

    • Canopy Group
    • Length (mm)(A)
    • Width (mm)(B)
    • Height (mm)(C)
    • Gross Weight Dry (kg.)
    • Full Tank Capacity (lt.)
    • AK 49
    • 3404
    • 1136
    • 2020
    • 1870
    • fueL_TANK_DETAILS_DRWGS

Optional Equipment

  • altEngine
  • altAlternator
  • altCabin
  • altControl Panel
  • altTransfer Board
  • altAuxiliary Equipment
  • altExhaust
  • altCabin Optionall

Engine

- Fuel-Water Seperator Filter

- Oil heater

Alternator Characteristics

- Anti-Condensation Heater

- Over sized alternator

- PMG excitation + AVR

- Main line circuit breaker

Canopy Characteristics

- Galvanized Coating

- ISO Container

- Marine Grade Paint

Control Panel

- Automatic synchronising and power control system (Multi gen-set Parallel)

- Parallel system with mains

- Transition synchronization with mains

- Alarm output relays

- Earth fault, single set

- Parallel system with mains

- Remote relay output

- Remote communication with modem

- Charge Ammeter

Transfer Panel

- Three or four pole contactor

- Three or four pole motor operated circuit breaker

Auxiliary Equipment

- Main Fuel Tank

- Automatic or manual fuel filling system

- Electrical or manual oil drain pump

- Low and high fuel level alarm

- Inlet and outlet motorized louvers

- Inlet and outlet acoustic baffles

- Tool kit for maintenance

- 1500/3000 hours maintenance kit

- Supplied with oil and coolant (-30°C)

Exhaust

- Residential Silencer

- Silencer Spark Arrester

- Critical Silencer

- Catalytic Convertor

Canopy Optional Alternator and Control Panel

Please contact to your reseller for additional Alternator, Control Panel and Breaker Switch options.

Certificates

Directive

- 2006/42/EC : Machinery Safety Directive

- 2014/30/EU : Electromagnetic Compatibility Directive

- 2014/35/EU : Low Voltage Directive

Standarts

- TS ISO 8528-5:2022 / TS EN ISO 8528-13:2018 : Reciprocating internal combustion engine-driven alternating

current generating sets- Part:13: Safety


Quality Management Systems

ISO 9001:2015

ISO 14001:2015

ISO 45001:2018

ISO 50001:2018

ISO 27001:2013

ISO 10002:2018


(Türkçe)

(English)

(French)

(Spanish)

(Russian)