APB 12500-T
- Home
APB 12500-T
APB 12500-T
Fuel Type Diesel- 220/380V
kVA
kW
Power Prime
11.9
9.52
Power Standby
12.5
10.00
General Features
Model Name APB 12500-T
Frequency (Hz) 50
Fuel Type Used Diesel
Engine Brand and Model -
Alternator Brand and Model Aksa - 245x130(T)
Control Panel Model HGM4020CAN
Cabinet APB 12500 KABIN
Product Features
-
Engine Specifications -
Alternator Features -
Control Panel Features -
Cabin Features -
Dimensions and Weights
Tab 1
Producer
Engine Model
Cylinder and Design
Bore and Stroke (mm)
X
Total Cylinder Volume (L)
Compression Ratio
Engine Speed (rpm)
Standby Power (kW/hp)
Prime Power(kW/hp)
Block Heater (Adt)
Block Heater Power (Watt)
Governor System
Air Filter<br>
Air intake
Oil Capacity (L)
Max. Oil Temperature ⁰C (F)
Fuel Type
Injection Type
Fuel Pump Type
Operating Voltage (Vdc)
Battery and Capacity (Unit/Ah)
Cooling Method
Coolant Capacity (engine only)l (gal)
Exhaust Gas Flow (m³/min)
Exhaust Back Pressure in-Hg (kPa)
Exhaust Gas Temperature ⁰C (F)
Total Cooling Water Capacity (l)
Cooling Fan Air Flow m³/min (ft³/min)
Fuel Consumption at 50% Prime Load l/h (kg/h)
Fuel Consumption at 75% Prime Load l/h (kg/h)
Fuel Consumption at 100% Prime Load l/h (kg/h)
Tab 2
Producer
Aksa
Alternatrr Model
245x130(T)
Frequency (Hz)
50
Voltage (V)
380
Phalse
3
A.V.R.
UNKNOWN
Voltage Regulation
1
Insulation Class
H
Protection Class
IP23
Tab 3
Generator and Control Module Model
HGM4020CAN
Standard Devices
132×64 backlit LCD display.
Selectable language support: Chinese, English, Spanish, Russian, Turkish, French, Portuguese, and Polish.
Push-button operation.
Durable hard acrylic screen protection with excellent wear and scratch resistance.
Silicone panel and buttons suitable for operation in extreme temperature environments.
RS485 communication interface supporting the following functions via MODBUS protocol:
- Remote Control
- Remote Monitoring
- Remote Communication
CANBUS communication port (HGM4020CAN model).
Compatible with engine ECUs supporting the J1939 protocol.
Enables monitoring of the following ECU parameters:
- Engine coolant temperature
- Oil pressure
- Engine speed (RPM)
- Fuel consumption
- Other essential engine parameters
CANBUS functions include:
- Engine start
- Engine stop
- Speed increase
- Speed decrease
Suitable for the following electrical system configurations:
- 3-Phase 4-Wire
- 3-Phase 3-Wire
- Single-Phase 2-Wire
- 2-Phase 3-Wire
Operating voltage:
- 120/240 V
Operating frequency:
- 50 Hz / 60 Hz
Measures and displays the following generator or mains parameters:
- Three-phase voltages
- Currents
- Power values
- Frequency
Warning Alarms
High Temperature
Low Oil Pressure
Gen Over Current
Fail to Stop
Low Fuel Level
Charge Alt Failure
Battery Under Volt
Battery Over Volt
Auxiliary Input
Loss of Speed Signal
Low Coolant Level
Temp. Sensor Open
Oil Pressure Sensor Open
Level Sensor Open
Temp. Sensor 2 Open
Oil Pressure Sensor 2 Open
Coolant Level Sensor Open
High Temperature 2
Low Oil Pressure 2
Low Coolant Level
Maintenance Due
Gen Over Volt.
Gen Under Volt.
Gen Over Freq.
Gen Under Freq.
Charge Alt Failure
Over Power
ECU Warn
Shutdown Alarms
Emergency Stop
Over Speed
Under Speed
Loss of Speed Signal
Over Frequency
Under Frequency
Over Voltage
Under Voltage
Over Current
Fail to Start
High Temp.
Low Oil Pressure
No Generate Electricity
Low Fuel Level
Low Coolant Level
Temp. Sensor Open
Oil Pressure Sensor Open
Fuel Level Sensor Open
Temp. Sensor 2 Open
Pressure Sensor 2 Open
Coolant Level Sensor Open
High Temp. 2
Low Pressure 2
Low Coolant Level
Maintenance Due
Over Power
Digital Input Port
ECU Alarm
ECU Comm. Failure
Tab 4
Canopy
APB 12500 KABIN
Length (mm)
1130
Width (mm)
750
Height (mm)
885
Tab 5
-
Open Group
-
Cabin Group
Tab 1

*Images are for illustrative purposes only; actual presentation may vary.
-
- Open Group
- Length (mm)(A)
- Width (mm)(B)
- Height (mm)(C)
- Gross Weight Dry (kg.)
- Full Tank Capacity (lt.)
-
- -
- -
- -
- -
- -
Tab 2

*Görseller temsilidir, sunumları farklılık gösterebilir.
-
- Canopy Group
- Length (mm)(A)
- Width (mm)(B)
- Height (mm)(C)
- Gross Weight Dry (kg.)
- Full Tank Capacity (lt.)
-
- APB 12500 KABIN
- 1130
- 750
- 885
- 241
- fueL_TANK_DETAILS_DRWGS
Optional Equipment
Certificates
Directive
- 2006/42/EC : Machinery Safety Directive
- 2014/30/EU : Electromagnetic Compatibility Directive
- 2014/35/EU : Low Voltage Directive
Standarts
- TS ISO 8528-5:2022 / TS EN ISO 8528-13:2018 : Reciprocating internal combustion engine-driven alternating
current generating sets- Part:13: Safety
Quality Management Systems
ISO 9001:2015
ISO 14001:2015
ISO 45001:2018
ISO 50001:2018
ISO 27001:2013
ISO 10002:2018