APB 44A

Product: Aksa Alternator: SC184J CONTROL SYSTEM: HGM6120CAN
INTRODUCTION

Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.

General Characteristics
Model Name APB 44A
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model Aksa - A4CRX37
Alternator Made and Model Aksa - SC184J
Control Panel Model HGM6120CAN
Canopy ACP 4-PB
3 Phase, 50 Hz, PF 0,8
VOLTAGE STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 44 35.20 40 32.00 63.51
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine Aksa
Engine Model A4CRX37
NO. OF CYLINDERS AND BUILD 4 cylinders - in line
BORE AND STROKE mm 98 X 120
TOTAL DISPLACEMENT L 3.6
Aspiration Naturally Aspirated
COMPRESSION RATIO 18:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 10
Standby Power (kW/HP) 42/56
Prime Power 37/50
Block Heater QTY
1
Block Heater Power (Watt)
500
Fuel Type
Diesel
Injection Type and System
Direct
Type of Fuel Pump
4I
Governor System
Mechanic
Operating Voltage (Vdc)
12 Vdc
Battery and Capacity (Qty/Ah)
1x54
Cooling Method
Water Cooled
Coolant Capacity (engine only) (l)
5
Total Coolant Capacity (l)
16
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (lt/hr)
10.4
ALTERNATOR SPECIFICATIONS
Manufacturer Aksa
Alternator Made and Model SC184J
Frequency (Hz) Hz 50
VOLTAGE V 400
Phase 3
A.V.R. MC460B
Voltage Regulation (+/-) 1
Insulation System H
Protection IP23
Rated Power Factor 0,8
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
ACP 4-PB
2086 950 1360 76
OPTIONAL EQUIPMENTS Engine

Oil heater

Alternator

3/4 Pole Output Circuit Breaker

Anti-condensation Heater

Transfer Panel

Charge ammeter

Transfer Switch 3Pole

Transfer Switch 4 Pole

Earth Fault, single set

Auxiliary Equipment

Bulk fuel tank

Automatic filling system

Fuel-water separator filter

Low fuel level alarm

Residential silencer

Enclosure or sound proof canopy

Trailer

Manual oil drain pump

Tool kit for maintenance

CONTROL SYSTEM: HGM6120CAN
Devices

1. Auto Mains Failure Control Panel


Panel Equipments:

  • Control with HGM module
  • Static battery charger
  • Emergency stop push button


A) Generating set control module HGM6120CAN features:

  • Configurable via PC software or the front panel
  • 5 programmable inputs (configurable for digital or analog signals)
  • 4 programmable relay outputs
  • Monitors 3-phase generator and mains (utility) voltage
  • Event log (50 records)
  • Configurable timers and alarm protection thresholds
  • Automatic shutdown or alarm upon fault detection
  • Supports remote start/stop and load transfer
  • Engine pre-heat control (relay output)
  • Precision measurement and display of engine and electrical parameters
  • Engine total run time accumulation
  • Red LED indicators for alarms/shutdown
  • LCD display with backlight, supports 8 language interfaces
  • Front panel test button
  • Modular design, flush mounting


B) Metering via LCD display:

  • Generator Voltage (L-L / L-N)
  • Generator Current (L1, L2, L3)
  • Generator Frequency (Hz)
  • Generator Power (Kw)
  • Generator Power Factor (COS Φ)
  • Accumulated Generator Energy (kWh)
  • Load Percentage (%)
  • Engine Oil Pressure (kPa / psi / bar)
  • Engine Temperature (°C / °F)
  • Fuel Level (%)
  • Battery Voltage (V)
  • Charger Voltage (V)
  • Mains Voltage (L-L / L-N)


C) Alarms:

  • Under Speed / Over Speed
  • Under Voltage / Over Voltage
  • Under Frequency / Over Frequency
  • Overload / Over Current / Overpower
  • Low Engine Oil Pressure
  • High Engine Coolant Temperature
  • Low Fuel Level (Optional)
  • Low / High Battery Voltage
  • Emergency Stop
  • Charge Fail
  • Sensor Open Circuit
  • Fail to Start
  • ECU Communication Failure (for EFI engines)
  • Maintenance Due
  • Aftertreatment System Related Alarms (foraftertreatment EFI gensets)


2. Power Outlet Terminal Board Mounted on the Gen-set Base Frame

GENERATING SET CONTROL UNIT


Canopy: ACP 4-PB
1. Steel structures. 
2. Emergency stop push button. 
3. Control panel is mounted on the baseframe . Located at the right side of the generator set. 
4. Corrosion-resistant locks and hinges. 
5. Oil could be drained via valve and a hose 
6. Exhaust system in the canopy. 
7. Special large access doors for easy maintanance 
8. In front and back side special large access doors for easy maintanance 
9. Base frame -fuel tank. 
11. The cap on the canopy provides easy accsess to radiator cap. 
12. Sound proofing materials 
13. Plastic air intake pockets.
INTRODUCTION
Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
STANDARD SPECIFICATIONS
Compact footprint, low profile design.
Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package
Body made from steel components treated with polyester powder coating
Fire retardant foam insulation
Easy access to all service points
Exhaust system inside canopy
Large doors on each side
Control panel viewing window in a lockable access door
Emergency stop push button mounted on enclosure exterior
Cooling fan and battery charging alternator fully guarded
Fuel fill and battery can only be reached via lockable access doors.
Lifting points on the top of canopy and base frame
Customer options available to meet your applications needs.
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest

CANOPY MODEL ACP 4-PB
WIDTH mm. 950
LENGTH mm. 2086
HEIGHT mm. 1360
TANK CAPACITY (lt.) Lt. 76