Product: Hyundai Alternator: AK 6480 CONTROL SYSTEM: InteliGen NT
INTRODUCTION

The new Twin Power series offers flexibility and performance like never before. With two gensets under one hood, it ensures backup and reliability twice. Two engines work in synchronization and back2back mode, which ensures a 24/7 power supply. The centralized control and monitoring system enables easy startup and commissioning. It provides savings in terms of total investment and operational costs to the customer.

General Characteristics
Model Name AD-TP 1420
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model Hyundai - DP180LB
Alternator Made and Model Aksa - AK 6480
Control Panel Model InteliGen NT
Canopy AK98 - 1420TP - Protection Class IP23
3 Phase, 50 Hz, PF 0.8
VOLTAGE STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 1420 1136.00 1280 1024.00 2049.65
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine Hyundai
Engine Model DP180LB
NO. OF CYLINDERS AND BUILD 10 cylinders - V type
BORE AND STROKE mm 128 X 142
TOTAL DISPLACEMENT L 18.273
Aspiration Turbo Charged and Intercooled (Air to Air)
COMPRESSION RATIO 15.0:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 34
Standby Power (kW/HP) 612/832
Prime Power 556/756
Block Heater QTY
1
Block Heater Power (Watt)
3000
Fuel Type
Diesel
Injection Type and System
Direct
Type of Fuel Pump
Bosh In-Line P Type
Governor System
Electronic
Operating Voltage (Vdc)
24 Vdc
Battery and Capacity (Qty/Ah)
2x120
Charge Alternator (A)
45
Cooling Method
Water Cooled
Cooling Fan Air Flow (m3/min)
700
Coolant Capacity (engine only) (l)
21
Total Coolant Capacity (l)
97.1
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (lt/hr)
136.4
Fuel Cons. Prime With %75 Load (lt/hr)
103.8
Fuel Cons. Prime With %50 Load (lt/hr)
71.2
ALTERNATOR SPECIFICATIONS
Manufacturer Aksa
Alternator Made and Model AK 6480
Frequency (Hz) Hz 50
Power (kVA) kVA 600
DESIGN   Brushless
VOLTAGE V 400
Phase 3
A.V.R. SX440
Voltage Regulation (+/-) 1
Insulation System H
Protection IP22
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 1543
COOLING AIR (m³/min) m3 62.1
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
AK98 - 1420TP - Protection Class IP23
11000 2050 3186
OPTIONAL EQUIPMENTS Engine

- Fuel-Water Seperator Filter

- Oil heater

Alternator

- Anti-Condensation Heater

- Over sized alternator

- PMG excitation + AVR

- Main line circuit breaker

Canopy

- Protection class IP 23

- Galvanized Coating

- ISO Container

- Marine Grade Paint

Control Panel

- Parallel system with mains

- Transition synchronization with mains

- Alarm output relays

- Earth fault, single set

- Parallel system with mains

- Remote relay output

- Remote communication with modem

- Charge Ammeter

Transfer Panel

- Three or four pole contactor

- Three or four pole motor operated circuit breaker

Auxiliary Equipment

- Main Fuel Tank

- Automatic or manual fuel filling system

- Electrical or manual oil drain pump

- Low and high fuel level alarm

- Inlet and outlet motorized louvers

- Inlet and outlet acoustic baffles

- Tool kit for maintenance

- 1500/3000 hours maintenance kit

- Supplied with oil and coolant (-30°C)

Exhaust

- Residential Silencer

- Silencer Spark Arrester

- Critical Silencer

- Catalytic Convertor

CONTROL SYSTEM: InteliGen NT

1. Start

2. Stop

3. Mode > OFF > MAN > AUT > TEST

4. Fault Reset

5. Mode < OFF < MAN < AUT < TEST

6. Horn Reset

7. GCB control (Open/Close)

8. MCB control (Open/Close)

9. Enter

10. 5% Increase of edited setpoint`s value.

11. 5% decrease of edited setpoint`s value.

12. Decrease setpoint value.

13. Increase setpoint value.

14. Escape.

Devices
InteliGen NT Auto Mains Failure control module.
Static battery charger.
Emergency stop push button and fuses for control circuits.
CONSTRUCTION and FINISH
Components installed in a sheet steel enclosure.
Phosphate chemical, pre-coating of steel provides corrosion resistant surface.
Polyester composite powder topcoat forms high gloss and an extremely durable finish.
Lockable hinged panel door provides for easy component access.
INSTALLATION
Control panel is mounted generating set baseframe on robust steel stand or power module. Located at the side of generating set with proper panel visibility.
GENERATING SET CONTROL UNIT

195Vac to 264Vac input voltage range

45Hz to 440Hz input supply frequency range

Capability to work direct from 240Vdc to 365Vdc supply voltage

27.6Vdc factory set DC out-put terminal voltage (option up to 29.4Vdc)

5.0Adc continuous output current into load

Capability to work continuously into short-circuit

Parallel connection for higher output current rating and redundant operation

Series connection capability for higher output voltage requirements

No cooling fans are used for high operational reliability

Aluminum alloy case for robust handling and easy mounting


Instruments
ENGINE
  • Engine Speed
  • Oil Pressure 
  • Water Temperature
  • Engine Runing Hours
  • Battery Voltage
  • Maintenance Plan

GENERATOR
  • Voltage (L-L, L-N)
  • Current (L1-L2-L3)
  • Frequency
  • Earth leakage
  • kW
  • Power Factor
  • kVAr
  • kWh, kVAh, kVArh

MAINS
  • Voltage (L-L, L-N)
  • Frequency

Options
  • High oil temperature - Shutdown
  • Low fuel level - Shutdown
  • Low fuel level - Alarm
  • High fuel level - Alarm
  • Customizable load control in parallel with the network
  • Wide range of ECU support
  • Highly configurable
  • Timers, Internal PLC, Force values and more are compatible with ComAp's InteliVision displays
  • Active e-mail messaging and SMS with communication modüle
Standards

EN 60068-2-6 ed.2:2008

EN 60068-2-27 ed.2:2010

EN 60068-2-30:2005

25/55°C, RH 95%, 48hours

EN 60068-2-64

EN 61010-1:2003

STATIC BATTERY CHARGER
EBC 2405M is designed and optimized for charging all types of Lead Acid batteries (including jell type sealed Lead Acid batteries), protecting the battery and extending its useful lifetime
EBC 2405M can deliver a continuous charging current of 5A into 24V battery system (voltage is set to 27.6Vdc, with an option of up to 29.4Vdc) These battery chargers are designed with performance in mind and special care is taken for protecting and extending the lifetime of the battery.
 
EBC 2405M is designed with “Switched Mode” technology, where the switching transistor has only two states, ON or OFF, which increases the overall efficiency, hence reducing the excess heat dissipation and in return, increasing the device lifetime and reliability.
 
The control system is also designed in such a way that; battery is charged in three stages:
 
Constant current mode (protecting battery cells)
 
Constant voltage mode (reducing the charge current)
 
Float charge (compensation of internal self-discharge)
 
Constant current mode makes sure that; when the battery is drained down below its rated capacity, the high charge current flow into the battery is limited in order to protect the cells and reduce damage to the plates.
 
As the battery capacity is recovered, each cell voltage reaches up to 2.30Vdc to 2.45Vdc level, which means that the required charging current starts to reduce.
 
When the required battery terminal voltage is fully reached, the charger keeps supplying just enough current in order to compensate for the internal self-discharge (float charge). This ensures that the battery can maintain its high charge state and deliver its rated output current whenever required.
 
Canopy: AK98 - 1420TP - Protection Class IP23
STANDARD SPECIFICATIONS


CANOPY MODEL AK98 - 1420TP - Protection Class IP23
WIDTH mm. 2050
LENGTH mm. 11000
HEIGHT mm. 3186
TANK CAPACITY (lt.) Lt.