APD-T 55 BD-S3A

Product: Baudouin Alternator: AK 351 CONTROL SYSTEM: D-500
INTRODUCTION

Aksa power generation system, providing optimum performance, and reliability, for stationary prime power exclusively for Telecommunication.. All generator sets are factory build, and production tested.

General Characteristics
Model Name APD-T 55 BD-S3A
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model Baudouin - 4M10G2D3/5
Alternator Made and Model Aksa - AK 351
Control Panel Model D-500
Canopy AKCELL-30
3 Phase, 50 Hz, PF 0.8
VOLTAGE STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 55 44.00 50 40.00 79.39
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine Baudouin
Engine Model 4M10G2D3/5
NO. OF CYLINDERS AND BUILD 4 cylinders - in line
BORE AND STROKE mm 105 X 118
TOTAL DISPLACEMENT L 4.09
Aspiration Turbo Charged and After Cooled
COMPRESSION RATIO 17.5:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 13
Standby Power (kW/HP) 66/89
Prime Power 60/81
Block Heater QTY
1
Block Heater Power (Watt)
750
Fuel Type
Diesel
Injection Type and System
Direct
Type of Fuel Pump
HPCR (High Pressure Common Rail)
Governor System
ECU
Operating Voltage (Vdc)
12 Vdc
Battery and Capacity (Qty/Ah)
1x66
Charge Alternator (A)
80
Cooling Method
Water Cooled
Cooling Fan Air Flow (m3/min)
125.7
Coolant Capacity (engine only) (l)
9.4
Total Coolant Capacity (l)
36
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (lt/hr)
14.21
Fuel Cons. Prime With %75 Load (lt/hr)
10.96
Fuel Cons. Prime With %50 Load (lt/hr)
7.71
ALTERNATOR SPECIFICATIONS
Manufacturer Aksa
Alternator Made and Model AK 351
Frequency (Hz) Hz 50
Power (kVA) kVA 64
DESIGN   Brushless
VOLTAGE V 400
Phase 3
A.V.R. SX460
Voltage Regulation (+/-) 1
Insulation System H
Protection IP22
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 311
COOLING AIR (m³/min) m3 12,96
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
AKCELL-30
2600 1272 1608
OPTIONAL EQUIPMENTS Auxiliary Equipment

- Ambient heater

- Resizable fuel tank

- Automatic or manual fuel filling system

- Electrical or manual oil drain pump

- Low and high fuel level alarm

- Inlet and outlet motorized louvers

- Inlet and outlet acoustic baffles

- Tool kit for maintenance

- 1500/3000 hours maintenance kit

- Supplied with oil and coolant (-30°C)

CONTROL SYSTEM: D-500
Menu navigation buttons 
Close mains button 
Main Status and instrumentation display 
Alarm LED's 
Close generator button 
Status LED's 
Operation selecting buttons
Devices
The D-500 is a next-generation genset control unit combining multi-functionality and wide communication possibilities together with a reliable and low-cost design.
CONSTRUCTION and FINISH
Storage temperature: -40°C to 80°C (-40 to +176°F)
Maximum humidity: 95% non-condensing.
IP Protection: IP65 from front panel, IP30 from the rear (with gasket)
Dimensions: 200 x 148 x 46mm (WxHxD)
Panel Cut-out Dimensions: 176 x 121 mm minimum.
Weight: 450 g (approx.)
Case Material: High Temperature, non-flammable ABS/PC
INSTALLATION
Installation: Flat surface mounting on a Type 1 enclosure. Rear retaining plastic brackets.
GENERATING SET CONTROL UNIT
• Battery back-up real-time clock
• Battery charge run enabled
• Battery voltage
STANDARD SPECIFICATIONS
• Fuel filling & fuel theft alarms
• Idle speed control
• Combat mode support
• Multiple nominal conditions
• Contactor & MCB drive
• 4 quadrant genset power
counters
• Mains power counters
• Fuel filling counter
• Fuel consumption counter
• Modem & ethernet diagnostics
• Configurable through USB,
 RS-485, Ethernet and GPRS
• Free configuration program
• Allows SMS controls
• Ready for central monitoring
Ethernet & GPRS
• Mobile genset support
• Automatic GSM geo-location
• GPS connectivity (USB&RS232)
Instruments
• Mains & genset PN/PP voltages
• Mains & genset frequency
• Mains & genset phase currents
• Mains & genset neutral currents
• Mains & genset, phase & total,
kW, kVA, kVAr, pf
• Engine speed
Protection Circuits
• Disable protections feature
• Excess power protection
• Reverse power protection
• Overload IDMT protection
• Load shedding, dummy load
• Multiple load management
• Current unbalance protection
• Voltage unbalance protection

Options
• 4-band GPRS modem (optional) 
Standards
EU Directives Conformity
 -2006/95/EC (low voltage)
 -2004/108/EC (electro-magnetic compatibility)
Norms of reference:
 EN 61010 (safety requirements)
 EN 61326 (EMC requirements)
UL & CSA Compatibility:
• UL 6200, Controls for Stationary Engine Driven
Assemblies (File# - 20140725-E314374)
• CAN/CSA C22.2 No. 14-13 – Industrial Control
Equipment
 
STATIC BATTERY CHARGER
Battery charger is manufactured with switching-mode and SMD technology and it has high efficiency.
Battery charger models' output V-I characteristic is very close to square
2405 has fully output short circuit protection and ıt can be used as a current source.
2405 charger has high efficiency, long life, low failure rate, lightweight and low heat radiated in accordance with linear alternatives.
The charger is fitted with a protection diode across the output.
Charge fail output is available.
Connect charge fail relay coil between the positive output and CF output.
Input: 196-264V.
Output: 27,6V 5A or 13,8V 5A.
Canopy: AKCELL-30
STANDARD SPECIFICATIONS


CANOPY MODEL AKCELL-30
WIDTH mm. 1272
LENGTH mm. 2600
HEIGHT mm. 1608
TANK CAPACITY (lt.) Lt.