APB 17 A
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
| Model Name |
APB 17 A |
||
|---|---|---|---|
| Frequency (Hz) |
50 |
||
| Fuel Type |
Diesel |
||
| Engine Made and Model |
Aksa - A4CRX21 |
||
| Alternator Made and Model |
Aksa - SC164D |
||
| Control Panel Model |
HGM6120CAN |
||
| Canopy | ACP 1A-PB |
| VOLTAGE | STANDBY RATING (ESP) | PRIME RATING (PRP) | Standby Amper | ||
|---|---|---|---|---|---|
| kVA | kW | kVA | kW | ||
| 400/231 | 17 | 13.60 | 16 | 12.80 | 24.54 |
PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
| Engine |
Aksa |
||
|---|---|---|---|
| Engine Model | A4CRX21 | ||
| NO. OF CYLINDERS AND BUILD | 4 cylinders - in line | ||
| BORE AND STROKE | mm | 85 X 95 | |
| TOTAL DISPLACEMENT | L | 2.156 | |
| Aspiration | Naturally Aspirated | ||
| COMPRESSION RATIO | 18:1 | ||
| RATED SPEED (RPM) | d/dk | 1500 | |
| OIL CAPACITY | L | 5.5 | |
| Standby Power (kW/HP) | 16.7/22.4 | ||
| Prime Power | 15.2/20.4 | ||
| Block Heater QTY | |||
| 1 | |||
| Block Heater Power (Watt) | |||
| 500 | |||
| Fuel Type | |||
| Diesel | |||
| Injection Type and System | |||
| Direct | |||
| Type of Fuel Pump | |||
| Direct | |||
| Governor System | |||
| Mechanic | |||
| Operating Voltage (Vdc) | |||
| 12 Vdc | |||
| Battery and Capacity (Qty/Ah) | |||
| 1x36 | |||
| Cooling Method | |||
| Water Cooled | |||
| Cooling Fan Air Flow (m3/min) | |||
| 112.64 | |||
| Coolant Capacity (engine only) (l) | |||
| 5.5 | |||
| Total Coolant Capacity (l) | |||
| 16.8 | |||
| Air Filter | |||
| Dry Type | |||
| Fuel Cons. Prime With %100 Load (lt/hr) | |||
| 4.59 | |||
| Fuel Cons. Prime With %75 Load (lt/hr) | |||
| 3.54 | |||
| Fuel Cons. Prime With %50 Load (lt/hr) | |||
| 2.6 | |||
| Manufacturer | Aksa | |
|---|---|---|
| Alternator Made and Model | SC164D | |
| Frequency (Hz) | Hz | 50 |
| VOLTAGE | V | 400 |
| Phase | 3 | |
| A.V.R. | MC460B | |
| Voltage Regulation | (+/-) | 1 |
| Insulation System | H | |
| Protection | IP23 | |
| Rated Power Factor | 0,8 | |
| Open Type | DRY WEIGHT (kg.) (kg.) |
LENGTH (mm.) |
WIDTH (mm.) |
HEIGHT (mm.) |
TANK CAPACITY (lt.) (Lt.) |
|---|---|---|---|---|---|
| CANOPY | DRY WEIGHT (kg.) (kg.) |
LENGTH (mm.) |
WIDTH (mm.) |
HEIGHT (mm.) |
TANK CAPACITY (lt.) (Lt.) |
ACP 1A-PB
|
1672 | 823 | 1127 | 32 |
Oil heater
3/4 Pole Output Circuit Breaker
Anti-condensation Heater
Charge ammeter
Transfer Switch 3Pole
Transfer Switch 4 Pole
Earth Fault, single set
Bulk fuel tank
Automatic filling system
Fuel-water separator filter
Low fuel level alarm
Residential silencer
Enclosure or sound proof canopy
Trailer
Manual oil drain pump
Tool kit for maintenance
1. Auto Mains Failure Control Panel
Panel Equipments:
- Control with HGM module
- Static battery charger
- Emergency stop push button
A) Generating set control module HGM6120CAN features:
- Configurable via PC software or the front panel
- 5 programmable inputs (configurable for digital or analog signals)
- 4 programmable relay outputs
- Monitors 3-phase generator and mains (utility) voltage
- Event log (50 records)
- Configurable timers and alarm protection thresholds
- Automatic shutdown or alarm upon fault detection
- Supports remote start/stop and load transfer
- Engine pre-heat control (relay output)
- Precision measurement and display of engine and electrical parameters
- Engine total run time accumulation
- Red LED indicators for alarms/shutdown
- LCD display with backlight, supports 8 language interfaces
- Front panel test button
- Modular design, flush mounting
B) Metering via LCD display:
- Generator Voltage (L-L / L-N)
- Generator Current (L1, L2, L3)
- Generator Frequency (Hz)
- Generator Power (Kw)
- Generator Power Factor (COS Φ)
- Accumulated Generator Energy (kWh)
- Load Percentage (%)
- Engine Oil Pressure (kPa / psi / bar)
- Engine Temperature (°C / °F)
- Fuel Level (%)
- Battery Voltage (V)
- Charger Voltage (V)
- Mains Voltage (L-L / L-N)
C) Alarms:
- Under Speed / Over Speed
- Under Voltage / Over Voltage
- Under Frequency / Over Frequency
- Overload / Over Current / Overpower
- Low Engine Oil Pressure
- High Engine Coolant Temperature
- Low Fuel Level (Optional)
- Low / High Battery Voltage
- Emergency Stop
- Charge Fail
- Sensor Open Circuit
- Fail to Start
- ECU Communication Failure (for EFI engines)
- Maintenance Due
- Aftertreatment System Related Alarms (foraftertreatment EFI gensets)
2. Power Outlet Terminal Board Mounted on the Gen-set Base Frame
Enclosure, generator set, exhaust system and base-tank are pre-assembled, pre-integrated and shipped as one package
Body made from steel components treated with polyester powder coating
Fire retardant foam insulation
Easy access to all service points
Exhaust system inside canopy
Large doors on each side
Control panel viewing window in a lockable access door
Emergency stop push button mounted on enclosure exterior
Cooling fan and battery charging alternator fully guarded
Fuel fill and battery can only be reached via lockable access doors.
Lifting points on the top of canopy and base frame
Customer options available to meet your applications needs.
| CANOPY MODEL | ACP 1A-PB | |
|---|---|---|
| WIDTH | mm. | 823 |
| LENGTH | mm. | 1672 |
| HEIGHT | mm. | 1127 |
| TANK CAPACITY (lt.) | Lt. | 32 |