APD-T 36 BD-S3A
Aksa power generation system, providing optimum performance, and reliability, for stationary prime power exclusively for Telecommunication.. All generator sets are factory build, and production tested.
| Model Name |
APD-T 36 BD-S3A |
||
|---|---|---|---|
| Frequency (Hz) |
50 |
||
| Fuel Type |
Diesel |
||
| Engine Made and Model |
Baudouin - 4M08G8D3/5 |
||
| Alternator Made and Model |
Aksa - AK 232 |
||
| Control Panel Model |
D-500 |
||
| Canopy | AKCELL-10 |
| VOLTAGE | STANDBY RATING (ESP) | PRIME RATING (PRP) | Standby Amper | ||
|---|---|---|---|---|---|
| kVA | kW | kVA | kW | ||
| 400/231 | 36 | 28.80 | 33 | 26.40 | 51.96 |
PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
| Engine |
Baudouin |
||
|---|---|---|---|
| Engine Model | 4M08G8D3/5 | ||
| NO. OF CYLINDERS AND BUILD | 4 cylinders - in line | ||
| BORE AND STROKE | mm | 98 X 105 | |
| TOTAL DISPLACEMENT | L | 3.17 | |
| Aspiration | Naturally Aspirated | ||
| COMPRESSION RATIO | 17.2:1 | ||
| RATED SPEED (RPM) | d/dk | 1500 | |
| OIL CAPACITY | L | 10.2 | |
| Standby Power (kW/HP) | 36/48 | ||
| Prime Power | 33/44 | ||
| Block Heater QTY | |||
| 1 | |||
| Block Heater Power (Watt) | |||
| 500 | |||
| Fuel Type | |||
| Diesel | |||
| Injection Type and System | |||
| Direct | |||
| Type of Fuel Pump | |||
| HPCR (High Pressure Common Rail) | |||
| Governor System | |||
| ECU | |||
| Operating Voltage (Vdc) | |||
| 12 Vdc | |||
| Battery and Capacity (Qty/Ah) | |||
| 1x55 | |||
| Charge Alternator (A) | |||
| 35 | |||
| Cooling Method | |||
| Water Cooled | |||
| Cooling Fan Air Flow (m3/min) | |||
| 97.5 | |||
| Coolant Capacity (engine only) (l) | |||
| 5 | |||
| Total Coolant Capacity (l) | |||
| 7.7 | |||
| Air Filter | |||
| Dry Type | |||
| Fuel Cons. Prime With %100 Load (lt/hr) | |||
| 8.49 | |||
| Fuel Cons. Prime With %75 Load (lt/hr) | |||
| 6.36 | |||
| Fuel Cons. Prime With %50 Load (lt/hr) | |||
| 5.18 | |||
| Manufacturer | Aksa | |
|---|---|---|
| Alternator Made and Model | AK 232 | |
| Frequency (Hz) | Hz | 50 |
| Power (kVA) | kVA | 40 |
| DESIGN | Brushless | |
| VOLTAGE | V | 400 |
| Phase | 3 | |
| A.V.R. | AS460 | |
| Voltage Regulation | (+/-) | 1,5% |
| Insulation System | H | |
| Protection | IP22 | |
| Rated Power Factor | 0.8 | |
| WEIGHT COMP. GENERATOR (Kg) | 226 | |
| COOLING AIR (m³/min) | m3 | 9 |
| Open Type | DRY WEIGHT (kg.) (kg.) |
LENGTH (mm.) |
WIDTH (mm.) |
HEIGHT (mm.) |
TANK CAPACITY (lt.) (Lt.) |
|---|---|---|---|---|---|
| CANOPY | DRY WEIGHT (kg.) (kg.) |
LENGTH (mm.) |
WIDTH (mm.) |
HEIGHT (mm.) |
TANK CAPACITY (lt.) (Lt.) |
AKCELL-10
|
2200 | 1200 | 1688 |
- Ambient heater
- Resizable fuel tank
- Automatic or manual fuel filling system
- Electrical or manual oil drain pump
- Low and high fuel level alarm
- Inlet and outlet motorized louvers
- Inlet and outlet acoustic baffles
- Tool kit for maintenance
- 1500/3000 hours maintenance kit
- Supplied with oil and coolant (-30°C)
Close mains button
Main Status and instrumentation display
Alarm LED's
Close generator button
Status LED's
Operation selecting buttons
Maximum humidity: 95% non-condensing.
IP Protection: IP65 from front panel, IP30 from the rear (with gasket)
Dimensions: 200 x 148 x 46mm (WxHxD)
Panel Cut-out Dimensions: 176 x 121 mm minimum.
Weight: 450 g (approx.)
Case Material: High Temperature, non-flammable ABS/PC
• Battery charge run enabled
• Battery voltage
STANDARD SPECIFICATIONS
• Fuel filling & fuel theft alarms
• Idle speed control
• Combat mode support
• Multiple nominal conditions
• Contactor & MCB drive
• 4 quadrant genset power
counters
• Mains power counters
• Fuel filling counter
• Fuel consumption counter
• Modem & ethernet diagnostics
• Configurable through USB,
RS-485, Ethernet and GPRS
• Free configuration program
• Allows SMS controls
• Ready for central monitoring
Ethernet & GPRS
• Mobile genset support
• Automatic GSM geo-location
• GPS connectivity (USB&RS232)
• Mains & genset PN/PP voltages
• Mains & genset frequency
• Mains & genset phase currents
• Mains & genset neutral currents
• Mains & genset, phase & total,
kW, kVA, kVAr, pf
• Engine speed
• Disable protections feature
• Excess power protection
• Reverse power protection
• Overload IDMT protection
• Load shedding, dummy load
• Multiple load management
• Current unbalance protection
• Voltage unbalance protection
• 4-band GPRS modem (optional)
EU Directives Conformity
-2006/95/EC (low voltage)
-2004/108/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
UL & CSA Compatibility:
• UL 6200, Controls for Stationary Engine Driven
Assemblies (File# - 20140725-E314374)
• CAN/CSA C22.2 No. 14-13 – Industrial Control
Equipment
Battery charger models' output V-I characteristic is very close to square
2405 has fully output short circuit protection and ıt can be used as a current source.
2405 charger has high efficiency, long life, low failure rate, lightweight and low heat radiated in accordance with linear alternatives.
The charger is fitted with a protection diode across the output.
Charge fail output is available.
Connect charge fail relay coil between the positive output and CF output.
Input: 196-264V.
Output: 27,6V 5A or 13,8V 5A.
| CANOPY MODEL | AKCELL-10 | |
|---|---|---|
| WIDTH | mm. | 1200 |
| LENGTH | mm. | 2200 |
| HEIGHT | mm. | 1688 |
| TANK CAPACITY (lt.) | Lt. | |